What are the installation requirements for fiberglass bridge frames?

2026-08-22 Visits:0

The installation of fiberglass bridge should strictly follow the corresponding standards to ensure the smooth construction of the installation project. The installation of fiberglass bridge has the following requirements:

When the length of the straight section fiberglass bridge exceeds 30m, and the length of the aluminum alloy or fiberglass bridge exceeds 15m, a compensating device shall be installed at the location where the expansion joint fiberglass bridge crosses the building deformation joint.

2. Fiberglass cable trays should be equipped with hangers or supports in the following locations:

2.1 At 0.5m from both ends of the bridge joint;

2.2 At intervals of 1.5-3m;

2.3 Turning point;

2.4 Vertical cable tray every 1.5 meters

3. The installation of hangers and brackets should be kept vertical, neat, firm, and without any tilting phenomenon.

4. The bolts of the bridge connecting plate are securely fastened without any omissions, and the nuts are located on the outside of the bridge.

5. Cable trays should be laid below flammable and explosive gas pipelines and thermal pipelines.